Abstract:Research purposes: Taking a planned rail transit control center that will use the BIPV/T technology as the study object and aiming at its differences from the conventional public buildings,this paper deeply studies the energy- saving effect by using the BIPV/T technology with the FLUENT and TRNSYS software to evaluate the energy-saving effect of the building.
Research conclusions: From the comparison and analysis it is concluded: (1)The annual generating capacity of the BIPV/T wall of the control center can be up to 128. 94 MWh.(2)The air-conditioning load for the BIPV/T wall of the control center can be much reduced by 4. 91 MWh in summer, dropping of 10. 21%.(3)The air-conditioning load for the BIPV/T wall of the control center can be reduced by 4. 48 MWh,dropping of 4. 15 %.(4)The heat production of the BIPV/T wall in winter can preheat the fresh air and it can effectively reduce the outdoor air heating load by 45. 18 MWh,dropping of 18. 11%.(5)This study result can provide the reference to the reasonable design and application of the BIPV/T technology for the special building like the control center of rail transit.
刘扬. 采用新型光伏墙体的轨道交通控制中心节能分析[J]. 铁道工程学报, 2013, 30(8): 108-114.
LIU Yang. Analysis of Energy-saving Effect of Rail Transit Control Center with New Type Photovoltaic Wall. 铁道工程学报, 2013, 30(8): 108-114.
Long Wenzhi. Building Integrated Photovoltaic and solar Thermal introduction[J].China Construction Metal Structure , 2009 ( 9 ) : 35-43.
[2]Gan G , Riffat SB. CFD Modelling of Air Flow and Thermal Performance of an Atrium Integrated with Photo Voltaics [J].Building and Environment , 2004 (39):735-748.
[3]Mei L , Infield D , Eicker U , etc. Thermal Modelling of a Building with an Integrated Ventilated PV Facade [J] .Energy and Buildings , 2003 ( 35 ) : 605-617.
[4]Zogou O , Stapountzis H. Energy Analysis of an Improved Concept of Integrated PV Panels in an Offlice Building in Central Greece [ J ].Applied Energy,2011 (88):853-866.
Fu Jiandong. Inspection Building Aluminum Glass Curtain Wall Exterior Building Envelope Energy- saving Design and Construction of Huanggang Port in Shenzhen Subway[J].Wall Materials Innovation& Energy Saving in Buildings , 2006 ( 7 ) : 48-50.
[10 ] The University of Wisconsin Solar Energy Laboratory. TRNSYS 16 Documentation [ M ].US : TRNSYS Group , 2007.
[11]Thermal Energy Systems Specialists ( TESS ) . TRNSYS 16 TESS Library Documentation [M].US: TESS, 2007.