Abstract:Research purposes: Shenzhen Futian Underground Railway Station has the characteristics of railway station and subway station and its underground space is not good for the person of suffering fire disaster to be relieved or escape.This paper studies the hierarchical management of the fire resource of underground railway station for the purposes of improving the safety management level and reducing the possibility of firing in underground railway station.
Research conclusions: Combining with the characteristics of service functions and structural style of the Futian Underground Railway Station,the fire resource of the station is identified,and the fire load and scale are analyzed,that is to take 2MW as the scale of luggage firing and manual setting fire,10MW as the scale of shopping fire and 16MW as the scale of train fire.According to the characteristics of underground space structure,the fire dangers in the different areas and the difficulty of evacuating persons,the method for 3 hierarchical management of fire resource is offered on the base of the different fire dangers and adopting the different fire monitoring modes and different management methods for the he different areas.
韩凤岩,徐志胜. 深圳福田地下火车站火灾危险源分级管理及优化设计[J]. 铁道工程学报, 2009, 26(5): 90-93.
HAN Feng—yan,XU Zhi—sheng. The Hierarchical Management of Fire Resource of Shenzhen Futian Underground Railway Station and Its Optimizing Design. 铁道工程学报, 2009, 26(5): 90-93.