Abstract:Research purposes:The number of subway station in construction or planning was huge in china, the quantity of makeup water for air conditioning recirculating cooling water in station which equipped with air conditioning was large,resulted in high operating costs and going against the economical use of water resources. And reclaimed water system of our city was developing gradually. Therefore,it was with great economic and social significance of feasibility research on using reclaimed water as makeup water for air conditioning recirculating cooling water in subway. The quality of air conditioning recirculating cooling water and the quality of city reclaimed water were analyzed and compared, deeper treatment program for reclaimed water was made,the technical and economic comparison of using reclaimed water and city water as air conditioning recirculating cooling water was made.
Research conclusions:(1)Using reclaimed water as air conditioning recirculating cooling water in subway is feasible, through pertinently advanced treatment,reclaimed water could be used as cooling water.(2)Although the initial investment of economic increases,but the operating cost is reduced.(3)On the whole,replenishment amount is bigger, the economic benefit is more.(4)The research provides a new idea for the choice of makeup water for air conditioning recirculating cooling water and the using mode of reclaimed water, which has a certain guiding significance to specific implementation.
杨伟帅,曾国保. 中水作为地铁空调循环冷却水补水可行性研究[J]. 铁道工程学报, 2014, 31(8): 105-109.
YANG Wei-shuai,ZENG Guo-bao. Feasibility Research on Using Reclaimed Water as Makeup Water for Air Conditioning Recirculating Cooling Water in Subway. 铁道工程学报, 2014, 31(8): 105-109.
Chen Jun,Li Yingchuan,Zhu Zhikun,etc. Technical Approaches to the Reuse of Municipal Mediun Cleaning Water in Industrial Cooling Water [ J ]. Industrial Water Treatment,2005(7) :13 -17.
[4] GB 50050—2007,工业循环冷却水处理设计规范[S].
GB 50050—2007, Code for Design of Industrial Recirculating Cooling Water Treatment [ S].
[5]陆耀庆.实用供热空调设计手册'M].北京:中国建筑工业出版社,2008.
Lu Yaoqing. Practical Design Manual of Heating and Air Conditioning [ M ]. Beijing : China Architecture & Building Press,2008.
[6] DB44/T 115—2000,中央空调循环水及循环冷却水水质标准[S].
DB44/T 115—2000,Standard for Recirculating Water and Recirculating Cooling Water Quality of Central Air Conditioning [ S].
Zhang Xiaoni,Liao Dongmei,Chen Mingjing. The Removal Experiment of Ammonia - Nitrogen in the Reuse of Municipal Wastewater for Circulation Cooling Water [ J ]. Central China Electric Power,2006 ( 4 ): 43 -45.
Jiang Lin,Li Hesheng,Wang Dong. Technology of Recycling Ammonia - Nitrogen Containing Wastewater to Circulating Cooling Water Systems [ J ]. Industrial Water Treatment,2007(4) :28 -30.