Abstract:Research purposes:The development of the platform above the car depot can greatly enhance the utilityvalue of land,and it is also the development direction in future. However,there is no existing criterion for this kind of building in China. The research was done on the individual fire protection of the Suzhou Taiping Car Depot,and a reasonable and feasible fire protection design and technological measures were proposed to satisfy the fire protection requirements. It can provide the reference to the similar works.
Research conclusions:From the research on the individual fire protection of the Suzhou Taiping Car Depot,the following points were concluded: (1) The fire protection design of the platform above the Suzhou Taiping Car Depot should considers the general development,the development by the car depot and property development,and some measures should be taken to satisfy the fire protection requirements.(2) The fire protections for the car depot and the property development should be completely separated by using the independent fire control systems with sharing the information in the fire control center.(3) The emergency exits to outdoor or the second floor platform should be installed for high or large building with crowds of people and big risks in the car depot. (4) The second floor platform that meets the requirements of load-bearing,rescue and turning of the large fire engine can be served as an outdoor safety area.(5) The second floor platform can be served as the outdoor ground surface of the building on the second floor according to the current design code for fire protection.
刘桂江;王栋. 苏州太平车辆段上盖开发消防设计[J]. 铁道工程学报, 2012, 29(11): 67-72.
LIU Gui-jiang,WANG Dong. Fire Protection Design for Development of Platform Above Suzhou Taiping Car Depot. 铁道工程学报, 2012, 29(11): 67-72.
Jiangsu Province Public Security Fire Department (plan) review the document [2011]No.1,Notice on the issuance of " Expert Review Meeting Minutes for Fire Protection Design for the top-head platform development of Suzhou Taiping Car Depot on Suzhou Rail Transit Line 2"[S].
Gao Hong.Research on the Development andDesign of Reserved Top-head Platform of Car Depot for Fire Protection[J].Journal of Railway Engineering Society,2009(6) : 107-110.