Study on the Interval Algorithm for Locating Fault of Railway Continuous Power Transmission Line |
XU Zhi—qiang,LI Bing,ZHANG Hai—bo,ZHOU Tian—hua,ZHANG Qiang |
Beijing Electric Power Transmission and Transformation Company,Beijing 102401,China |
|
|
Abstract Research purposes: High reliability of power supply is required for railway continuous power transmission line,however,the single—phase—to—ground fault often occurs on the lines,which Can cause power supply interruption and bring the risk to the traffic safety.How to precisely diagnose and quickly eliminate the single—phase—to—ground fault has become a problem to be solved urgently for the railway departments.The accuracy of fault location call not meet the requirement of rapid sectioning the fault with the impedance method and traveling wave method.According to the structural characteristics of the railway continuous power transmission line and the requirements of the rapid sectioning the fault,the study is done on the method for the interval location.
Research conclusions: Through the study,the lumped parameter interval algorithm,fault network decomposing interval algorithm and distributed parameter interval algorithm were deduced by using interval analysis method.The PSCAD simulation analysis Was made for the actual transmission line model to verify the feasibility of interval location method.In order to further test its practicability in engineering,the field simulated tests were done with the three algorithms for railway continuous power transmission line from Kaili to Fuquan.The tested results fully met the requirements of precision and rapidity for fault location.Both the theoretical calculation and factual tests had shown that the using Interval algorithm could effectively solve the problem of fault location railway continuous power transmission line.
|
Received: 30 October 2009
|
|
|
|
|
[1] T. Takagi, Y. Yamakoshi, M. Yamaura R. Kondow. Development of a New Type Fault Locator Using the One -Terminal Voltage and Current Data [J]. IEEE Transactions of Power Apparatus and Systems, 1982, 101(8): 2892 -2897.
[2] Girgis A A, Hart D G, Peterson WL. A New Fault Location Technique for Two and Three-terminal Lines [J]. IEEE Transon Power Systems, 1992, 7(1): 98 - 107.
[3] 葛耀中.新型继电保护与故障测距原理与技术[M ].西 安:西安交通大学出版社, 1996.
Ge Yaozhong. New Types of Protective Relaying and Fault Location Theory and Techniques [M ]. Xi ' an: Xi'an Jiaotong University Press, 1996.
[4] 徐丙垠,李京,陈平,等.现代行波测距技术及其应用[J]. 电力系统自动化, 2001(23): 62 -65.
Xu Bingyin, Li Jing, Chen Ping, eta.l M odern Fault Location Techniques Based on Fault Generated Traveling Waves and Their Applications [ J ]. Automation of Electric Power Systems. 2001(23): 62 - 65.
[5] 季涛,高旭,孙同景,等.铁路10kV自闭/贯通线路故障 行波特征分析[J].山东大学学报, 2006(2): 111 -116.
Ji Tao, Gao Xu, Sun Tongjing, eta.l Characteristic Analysis of Fault Generated Traveling Waves in 10 kV Automatic Blocking and Continuous Power Transmission Lines [ J ]. Journal of Shandong University, 2006(2): 111 -116.
[6] 邵华平,何正友,钱请泉,等. 10kV铁路输电线路故障信 息综合处理系统研究[J].西安交通大学学报, 2004(8): 869 -872.
Shao Huaping, He Zhengyou, Qian Qingquan, eta.l Comprehensive Research on Transmission L ine Fault Information for 10kV Railway Power System [ J ]. Journal fo Xi'an Jiaotong University, 2004 (8): 869 - 872.
[7 ] R. E, Moore. Methods and Applications of Interval Analysis[M]. SIAM Publications 1979.
[8 ] Luc Jaulin, Michel Kieffer, Olivier Dirit. Applied Interval Analysis [M]. Springer Verlag, London, 2001.
[9] R. E, Moore. On Computing the Range of Values of a Rational Function of n Variables Over a Bounded Region. Computing. 1976, 16: 1 -15.
[10 ]Renpu Ge. Optimal Choice of Linear Interval Extension. Applied Mathematics and Computation. 1989, 30: 165 -189.
[11]铁道部专业设计院.铁路工程设计技术手册(电力) [K]. 北京:中国铁道出版社, 1991.
Professional Design Institute for Ministry of Railway. Railways Engineering Designing Manual(Electric) [K]. Beijing: China Railway Publishing House, 1991.
|
|
|
|